the poles of the rotor moves under the armature conductor on the stator , field flux cuts the armature conductors. therefor voltage is generated in these conductors.  the voltage is of alternating nature, since poles of alternate polarity successively pass by a given stator conductor.  A 3-phase alternator has a stator with three set of windings. arranged so that is a matual phase displacement of 120 . these winding are connected in star to a 3-phase output.the voltage generated in each winding is given as equation is called emf equation.
Let, 
     Î¦  =  useful flux per pole in webers
      P  =  total number of poles
     Zp =  total
number of conductors
     Tp  =  total number of coils or tuns per phase
      n = speed of rotation of rotor in revolution per second (r.p.s.)
      f  = frequency of generated voltage ( Hz )
Since the flux per pole is Φ , each stator conductor cuts flux PΦ.
The average value of generated voltage per conductor 
              =            flux cut per revolution in Wb        
                   time taken for one revolution in seconds
Since n revolution are made in one second, one revolution will be made in 1/n second. therefore the time for one revolution of the armature is 1/n second.
  
Eav/ conductor = PΦ   = nPΦ     .....................................(1).
                           1/n
We know that 
                        f = PN/120 =  Pn/2
                      Pn = 2f
these value put in equation 1 we get ,
 Eav/ conductor = 2fΦ           ........................................(2).
sinc there are  Zp  conductor in series per phase , the average voltage generated per phase is given by
       Eav/ phase = 2fΦ Zp
since one turn or coil has two sides Zp = 2Tp  , the expression for the average generated voltage per phase can be written as
Eav/ phase = 4fΦTp
for voltage wave , the form factor is given by 
                     Kf = r.m.s.  value/ average value
For a sinusoidal voltage , Kf =1.11 . therefore . the r.m.s. value of generated voltage per phase can be written as 
    Er.m.s. / phase = Kf x Eav / phase = 1.11 x 4fΦTp = 4.44fΦTp
the r.m.s. value of generated voltage per phase is given by 
Ep =  4.44fΦTp
Equation has been derived with the following assumptions:
- Coil have got full pitch.
- all conductor are concentrated in one stator slot.