In an a.c. machine, any flux setup by load current which
does not contribute to the useful flux of the machine is a leakage flux. the
effect of this leakage flux is to setup self induce emf in the armature
winding.
the leakage flux may be classified as following.
1. Slots leakage
2. tooth head leakage
3. coil end or overhanging leakage
the voltage induce in the armature
windings by air gap flux is called air gap voltages .
The leakage flux also induce voltage in the armature
windings. these taken into account by introduction of leakage reactance drops.
Most of reluctances of the magnetic circuits for armature leakage fluxes are
due to air paths. The fluxes are , therefore , nearly proportional to the
armature currents producing them and are in phase with these currents. For this
reason , the voltage induce in the armature winding can be taken into account
by use of constant leakage reactance for the phases , which multiplied by the
phasor currents , give the component voltages induce in the phases by leakage
flux . these voltage are the leakage reactance drops and lead the currents
producing them by 90 degree.
This leakage flux makes the armature
winding inductive in nature. So winding possesses a leakage reactance, in
addition to the resistance.
The effect of armature flux in an
alternator depends on Magnitude
of current flowing through the armature winding and Nature of power factor
of the load connected to the alternator.
the synchronous reactance of an alternator
is equal to Sum
of leakage reactance and armature reaction reactance.